Medium voltage sectioning cabinet – CS

Medium Voltage 15 kV and 36 kV Sectioning Cabinet – CS, with branching of more output lines from an existing cabinet, using disconnectors with HH fuse base and fuses intended for protection. 

Application

In utility substations, for protection and main disconnection of factories and industrial facilities, pumping stations, railway systems, and electric power generation plants.

Technical and specific characteristics

– Fully shielded cubicle made of galvanized steel sheet from the factory.

– Roof with a slope to allow rainwater to drain.

– Metal partitions forming independent compartments.

– Front and rear doors equipped with internal hinges and latches.

– Protective grilles made with protective mesh in the interior access openings.

– Pressure relief valves to protect against internal arcs.

– Electrolytic copper busbars sized according to ABNT standards.

– Epoxy insulators, guaranteeing total resistance to stress.

Internal grounding system.

– Devices for seals, arranged according to the standards of the concessionaires.

– The medium voltage substation is equipped with a metal cover for protection against accidental contact with live parts inside and against water ingress, in accordance with ABNT NBR IEC 60529.

– Covers, doors, and other metal parts receive anti-corrosion treatment and paint suitable for the conditions in which they will be installed.

Technical Data

Technical Information

 

Feature Specification
Class 15 | 25 | 36
In (A) 400¹
Ic (kA) 12,5
Voltage supplied at industrial frequency (kV) 38 | 50 | 70
NBI (kV) 95 | 125 | 170
Control voltage (Vac) 115¹
Auxiliary service voltage (Vac) 115¹
Applicable standards² NBR IEC 62271-200
Degree of protection IP-54
Installation type External
sheet material Galvanized steel
Sheet thickness 14MSG (1.9mm)
Cable entry and exit Lower
Maximum altitude above sea level (m) 1.000
Busbars Copper³
Type of paint Electrostatic powder
Color Munsell Gray N6.5¹

 

Notes and additional information

ACCESSORIES

– Protective fuses

Interconnecting cables are also items that may be included with the product.

IMPORTANT INFORMATION

Another possible application is as a direct protection cabinet, provided the installed power does not exceed 300 kVA.

The cabin must initially be powered on without any load, i.e., without any transformer connected to the output, to verify that it is in compliance for operation.

Before carrying out any work, make sure the cabin structure has been grounded.

Downloads

Related Products