Compact primary substation developed for medium voltage 15 kV entry, metering, switching and protection – CCMP
Home > Products > Substations > Metal cabins > Medium voltage primary incoming and metering substation – CCMP
Compact primary substation developed for medium voltage 15 kV entry, metering, switching and protection – CCMP
Application
In utility substations, for protection and main disconnection of factories and industrial facilities, pumping stations, railway systems, and electric power generation plants.
Technical and specific characteristics
– Fully shielded cubicle made of galvanized steel sheet from the factory.
– Roof with a slope to allow rainwater to drain.
– Metal partitions forming independent compartments.
– Front and rear doors equipped with internal hinges and latches.
– Protective grilles made with protective mesh in the interior access openings.
– Pressure relief valves to protect against internal arcs.
– Electrolytic copper busbars sized according to ABNT standards.
– Epoxy insulators, guaranteeing total resistance to stress.
Internal grounding system.
| Feature | Specification |
| Class | 15 | 25 | 36 |
| In (A) | 400¹ |
| Ic (kA) | 12,5 |
| Voltage supplied at industrial frequency (kV) | 38 | 50 | 70 |
| NBI (kV) | 95 | 125 | 170 |
| Control voltage (Vac) | 115¹ |
| Auxiliary service voltage (Vac) | 115¹ |
| Applicable standards² | NBR IEC 62271-200 |
| Degree of protection | IP-54 |
| Installation type | External |
| sheet material | Galvanized steel |
| Sheet thickness | 14MSG (1.9mm) |
| Cable entry and exit | Lower |
| Maximum altitude above sea level (m) | 1.000 |
| Busbars | Copper³ |
| Type of paint | Electrostatic powder |
| Color | Munsell Gray N6.5¹ |
IMPORTANT INFORMATION
Specific characteristics of the materials used must be defined during the product quotation process.
The cabin must initially be powered on without any load, i.e., without any transformer connected to the output, to verify that it is in compliance for operation.
Before carrying out any work, make sure the cabin structure has been grounded.