iGrid Voltage Regulator

The Romagnole iGrid Voltage Regulator is a single-phase device for automatic correction of voltage levels in overhead distribution networks and substations. The regulator monitors the circuit voltage and operates the on-load tap changer without interrupting the supply, compensating for load variations, voltage drops, and flow changes caused, among other things, by the presence of distributed generation.

Regulation is performed in 33 positions: 16 for raising, 16 for lowering, and the neutral position, with steps of 0.625%, totaling a range of ±10%. In three-phase banks, each regulator acts on its phase, and the control can coordinate the set to reduce imbalances and avoid inappropriate switching sequences.

Application

  • Specific adjustments for networks with cogeneration and distributed generation, including reverse flow operation.
  • TAP ZERO function for automatic return to neutral position.
  • Recording of events, operations, and measurements for operational analysis and maintenance.
  • Voltage limiter: speeds up correction when voltage exceeds extreme set limits.
  • Current limiter: blocks switching when the current exceeds the configured limit.
  • Reverse flow detector: adapts the source and load reference according to the direction of the power.
  • Data acquisition and measurement history for network diagnostics.
  • Check Tap and transaction counting for tracking bank position and synchronization.
  • IEC 60870-5-101, IEC 60870-5-104 and DNP3.0 protocols. IEC 61850 compliance with other control models.
  • Sensing of vibration, pressure, temperature, and other parameters for real-time monitoring and historical performance data (optional).
  • Application of artificial intelligence for pattern detection, maintenance prediction, and service life (optional).

Technical and specific characteristics

  • Compliant with IEEE C57.15, IEC 60076.
  • Automatic load regulation, without interruption of supply during position change.
  • 33 operating positions: ±16 of 0.625% plus the neutral position.
  • Total regulation range of ±10% per regulator.
  • Single-phase free or assisted operation and three-phase synchronized operation via control.
  • Compatibility with UPS, allowing for pre-defined positioning of the switch during power outages and fault indication.
  • Switching protection due to overcurrent or undervoltage.
  • Magnetic position indicator, without mechanical connection through the tank, reducing potential points of leakage or water ingress.
  • Compatible with universal remotes and available with or without integrated remote control.
  • Vegetable oil as an option for insulating fluid.
  • Complete book of the project tested and approved by KEMA Labs.

Technical Data

Technical Information

Technical data

 

 

Switch

On-load tap changer – 33 positions: ±16 steps + zero position
Regulatory step 0.625% per position
Regulation range ±10%
NBI Up to 200 kV, according to the selected nominal rating.
Frequency 50 or 60 Hz, depending on the configuration.
Assembly Post or platform, as configured.
Insulating fluid Mineral oil or vegetable oil
Construction accessories Pressure relief valve, oil level indicator, magnetic position indicator, tank grounding, bushings and surge arresters between source and load.
Standards cited in the sources IEEE C57.15, IEC 60076 and ABNT NBR 11809

Notes and additional information

Preferred nominal classifications

System
(kV)
Freq.
(Hz)
Nominal voltage
(V)
NBI
(kV)
Power
(kVA)
Current
(THE)
5 60 2,500 / 4,330Y 60 50 to 167 200 to 668
6,6 50 6.600 75 33 to 396 50 to 600
8,7 60 5,000 / 8,660Y 95 / 110 50 to 333 100 to 668
11 50 6.530 / 11.000Y 95 / 110 32 to 381 50 to 600
11 50 11.000 95 / 110 55 to 660 50 to 600
15 60 7.620 / 13.200Y 95 / 110 38.1 to 509 50 to 668
15 60 13.800 95 / 110 69 to 833 50 to 604
15 50 15.000 95 / 110 75 to 600 50 to 400
25 50 14.400 / 24.940Y 150 72 to 833 50 to 578
25 50 22.000 150 110 to 880 50 to 400
35 60 19.920 / 34.500Y 170 / 200 100 to 833 50 to 418